1. Connect Nautilus Air
2. Calibrate using your phone
Nautilus-Air-XXXXXX (the suffix is printed for your unit). Wi-Fi password: Nautilus. Open http://192.168.4.1 in your browser.Advanced sensor setting: automatic baseline calibration (ASC)
ASC is a separate SCD40 feature from manual calibration. The beta firmware provides an ON/OFF status and setting in Advanced Settings. OFF is generally recommended for reef rooms that may not regularly return to fresh-air conditions. Do not change it without understanding the effect on long-term calibration.
3. Apex: create an example virtual outlet
A virtual outlet is a software control state; it does not itself supply electricity. Choose an unused virtual output, name it Air_CO2, select Advanced and put it in AUTO.
Example virtual output programming
Set OFF If CO2 > 500 Then ON If Error Apex Then OFF
Substitute your actual Apex input name for CO2. This example switches the virtual output ON above 500 displayed units and requests OFF if Apex detects a module error. Its last line must remain after the ON condition.
If Error Apex condition is a broad module-error rule, not a sensor-specific heartbeat.4. Controlling equipment (for example, a fan)
For a suitable non-critical device, select the physical Energy Bar outlet powering it. Set that outlet to Advanced and AUTO and enter the following, replacing Air_CO2 if your virtual outlet has a different name:
Example physical outlet programming
Fallback OFF Set OFF If Output Air_CO2 = ON Then ON
The physical outlet follows the virtual outlet. Fallback OFF concerns communication to the output module; it does not itself detect FMM sensor loss.
If Error Apex Then OFF in the virtual outlet, the physical test fan took approximately 100 seconds to turn OFF. This is not an instantaneous safety cutoff. Choose a safe failure state for each application; for some ventilation installations, OFF may not be the safest state.5. Troubleshooting and after testing
- Zero reading: Check Nautilus Air USB power, whether the SCD40 is running, the jack seating and the FMM port configuration. Zero may mean signal loss, not clean air.
- Frozen reading: Check FMM module status in Apex Modules. A disconnected FMM can leave its last number visible.
- Local and Fusion disagree: Allow time for dashboard updates; compare stable readings with the device's live measurements.
- Calibration unclear: Wait for explicit success; don't keep applying calibration to chase an immediate number.
- After testing: Restore any previous Apex outlet programming and settings, and validate all equipment behaviour.